Inert gas fire suppression for data centers

Inert-gas systems lower the oxygen in the hall below what a fire needs. Fifteen companies here sell them, from Fire Eater’s Inergen (52% nitrogen, 40% argon, 8% carbon dioxide) to NAFFCO’s IG-01, IG-100, IG-55 and IG-541 and Nohmi’s NN100 IG-100 nitrogen system. The selection questions are storage pressure, cylinder count, pipe run and discharge noise.

15 companiesChecked

Agents and productsAcoustic designApprovals
FikeManufacturerSF 1230 Fire Protection Fluid offered as a one-to-one drop-in Novec 1230 replacement———2026-11-11
Fire Eater—Inergen: nitrogen 52%, argon 40%, carbon dioxide 8%——Hillerød, Denmark2026-11-11
FOGTECManufacturer and installer———Cologne, Germany2026-11-11
Gielle IndustriesInstaller / serviceIG-01, IG-100, IG-55 and IG-541 inert gases———2026-11-11
Janus Fire SystemsManufacturerFK-5-1-12, FM-200 and IG-100 inert-gas systems——Crown Point, Indiana, United States2026-11-11
Johnson Controls (Ansul, Tyco, LPG)Manufacturer and installerSAPPHIRE and FM-200 halocarbon systems (LPG brand)———2026-11-11
Kidde Fire Systems (KiddeFenwal)ManufacturerNATURA inert gas, Fluoro-K and HFC-227ea clean agentsNATURA Acoustic Nozzles: below 110 dB over 500 Hz–10 kHz, measured at 1 m——2026-11-11
MinimaxManufacturerOxeo inert gas and MX 1230 systems———2026-11-11
NAFFCOManufacturer and installerNAFFCO Inert offers IG-01, IG-100, IG-55 and IG-541—Inert-gas suppression system UL listed and FM approvedJebel Ali Free Zone, Dubai, UAE2026-11-11
Nohmi BosaiManufacturer and installerNN100 IG-100 nitrogen gas suppressionPNQ/ZMQ series noise reduction nozzlesNN100 is UL listedTokyo, Japan2026-11-11
Rotarex FiretecManufacturerINEREX total-flooding inert gas and RX5112 FK-5-1-12 systems—INEREX product line supports VdS, UL and FM approved inert-gas systemsLintgen, Luxembourg2026-11-11
Scutum—————2026-11-11
Siemens (Sinorix)ManufacturerNitrogen and argon inert gasesSinorix Silent Extinguishing Technology with SDNX silent nozzle—Zug, Switzerland2026-11-11
Viking GroupManufacturer——Data Center Upgradeable System is UL ListedMichigan, USA2026-11-11
WAGNER GroupManufacturerFirExting gas extinguishing with nitrogenFirExting SILENT nozzle silencers for sensitive electronics——2026-11-11

How inert-gas systems differ

How fields are read

Storage pressure and cylinder size

NAFFCO and Gielle both list 200 or 300 bar storage (Gielle). NAFFCO offers 67, 80 and 140 litre cylinders with a regulated pressure of 60 bar. Higher pressure means fewer cylinders for the same hall.

A real reference

Fire Eater protects CSC’s Kajaani data center, home to the LUMI supercomputer, with 153 cylinders of Inergen and about 800 m of pipe, covering 5,700 m³.

Noise

Inert-gas discharge is loud, and several makers sell quiet nozzles: Wagner’s FirExting SILENT silencers, Siemens’ Sinorix Silent Extinguishing Technology and Nohmi’s PNQ/ZMQ nozzles. Kidde’s NATURA acoustic nozzles are below 110 dB over 500 Hz to 10 kHz at 1 m.

Prevention instead of discharge

Wagner’s OxyReduct generates nitrogen from ambient air to hold oxygen low all the time, rather than flooding the room after detection.

Prefer a halocarbon? See clean agent suppression. Want no gas at all? See water mist and preaction.